Uses
Monitoring fluid flow in:
- Air Conditioning Systems
- Industrial Refrigeration Systems
- Cooling in Data Centers
- Pools and Spas
- Chillers
- Scrubbers
- Fluid Blending Systems
- Water Treatment Systems
- Natural Gas
Monitoring fluid flow in:
PIPE SIZE NPT
|
NOMINAL ON/OFF |
SHAFT LENGTH
|
PADDLE NUMBER
|
|
---|---|---|---|---|
SWITCH POINT RANGE | Model | |||
(GPM) | ||||
1″
|
5.0 – 3.0 | – | 10512 | CF-8N/-/10512 |
9.6 – 7.5 | 1 | 2 | CF-8N/1/2 | |
15.4 – 18.0 | 1 | 1 | CF-8N/1/1 | |
1 1/2”
|
12.0 – 9.5 | – | 10502 | CF-8N/-/10502 |
14.2 – 11.8 | 2 | 3 | CF-8N/2/3 | |
19.0 – 13.5 | – | 10570A | CF-8N/-/10570A | |
22.5 – 19.0 | 2 | 2 | CF-8N/2/2 | |
34.4 – 30.4 | 2 | 1 | CF-8N/2/1 | |
2″
|
14.4 – 10.2 | – | 10593 | CF-8N/-/10593 |
16.5 – 11.0 | – | 10566 | CF-8N/-/10566 | |
25.8 – 21.8 | 2 | 3 | CF-8N/2/3 | |
39.8 – 33.6 | 2 | 2 | CF-8N/2/2 | |
58.0 – 50.8 | 2 | 1 | CF-8N/2/1 | |
3″
|
42.4 – 37.0 | 3 | 3 | CF-8N/3/3 |
55.6 – 49.8 | 3 | 2 | CF-8N/3/2 | |
80.6 – 65.2 | 3 | 1 | CF-8N/3/1 | |
* /1G = Two Recepticals: one always on & one switched | ||||
* /2G = Four Recepticals: two always on & two switched (shown) | ||||
* Tee not included |
CF8 Group |
CF-8-1G |
CF-8-2G | |
CF-8CR-1G | |
CF-8CR-2G |
HYSTERESIS (Δ FLOW RATE TO ACTIVATE/DEACTIVATE SWITCH)
≈ 10% at upper end of flow range
≈ 30% at lower end of flow range
DIFFERENTIAL PRESSURE DROPS ACROSS UNIT
Under normal operating conditions:
≈ 1″–3″ pipe, less than 0.5 psi
≈ 4″–10″ pipe, negligible
WORKING LINE PRESSURE:
50 psi max., operating @ 180˚F 100 psi max. non-operating @ 180˚F Pressure over 50 psi can affect the switch point range
ELECTRICAL SWITCH CHARACTERISTICS
SPDT (single pole double throw) 13A, ½ hp @ 125VAC ½A @ 125VDC (tungsten lamp load) 10,000,000 Operations Median